Facts

Specifications, test evidence and deployment rules for OWL and ATHENA.

OWL

Bus
RS-485, 2-wire, connected in parallel at A, B and REF
Protocols
Modbus RTU and DNP3 serial
Bus speed
Eight standard speeds from 1200 to 115200 baud, detected from the traffic. The receiver's limit is 200 kbps.
Character format
8N1, 8E1, 8O1, 8N2, detected from the traffic
Receiver
Galvanically isolated, wired receive-only
Isolation gaps on the board
Bus to logic 6.1 mm. Output to logic 6.3 mm.
Load on the bus
1 k in series with each line. A shorted protection diode loads the bus with 2 k.
Supply
24 V DC, under 2 W. Fused, reverse-protected, monitored.
Processor
RP2350 (Raspberry Pi Pico 2). No radio.
Link to ATHENA
One-way optocoupler, 3 wires, 230400 baud, about 3 m of cable
Heartbeat
Once a second, so a dead tap is never read as a quiet bus
Front panel
Three lights: PWR, RX, ALM. No display.
Case
35 mm DIN rail, 3 modules. 54 x 90 x 58 mm.

ATHENA

Decoding
Modbus RTU and DNP3 serial, one protocol per bus
Platform
Raspberry Pi 3B or 4. One static binary, 4.1 MB.
Storage
SQLite on the Pi. A power cut loses at most the last second of frames.
Retention
Frames: 7 days or 5 million rows. Detections, baseline revisions and the audit log are kept.
Output
JSON lines, or RFC 5424 syslog over UDP or TCP
Accounts
Named local accounts. Three roles. Audit log.
Network
Needs no internet access.